![FujiFilm PXG4 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483031.webp)
– 30 –
4
Chapter
Overview of Control (PID) Parameters (Ch2)
This section explains parameters related to PID and other controls.
The PID menu contains the following items.
Note 1: Displays when the fifth digit of the model code is not S or V, and the sixth digit is A, C, E or P.
Note 2: Make sure to set the values for "
SSS
SvvvvLLLL
" and "
SSS
Svvvvhhhh
" so that SvL is less than Svh. When the set values of “SVL” and “SVH” are
changed, adjust SV set value 1 (“Sv1 Ch3”) through SV set value 7 (“Sv7 Ch3”).
Note 3: Displays when the fifth digit of the model code is A or C.
Note 4: Turn off the power to the unit after changing the parameters with
in the remarks column.
Note 5: The parameters in the shaded area indicates the industrial values.
Display
Parameter name
Function
Setting range
Initial
value
Remarks
Page
"
P
" (P)
Proportional band
Sets the proportional band for the PID
parameter.
Setting to 0.0 will revert to ON/OFF control.
0.0% to 999.9%
5.0%
31
"
I
" (I)
Integration time
Sets the integration time for the PID
parameter.
Setting "0" will turn off integration.
0 sec to 3200 sec
240 sec
"
d
" (d)
Derivative time
Sets the derivation time for the PID
parameter.
Setting "0.0" will turn off derivative.
0.0 sec to 999.9 sec
60.0 sec
"
hyS
" (hyS)
ON/OFF control
hysteresis
Sets the hysteresis width for the on/off
control.
0% to 50% FS
1°C
32
"
CoL
" (CoL)
Cooling proportional
band coefficient
Sets the cooling proportional band coefficient
Setting "0.0" will turn the cooling into an on/off
control.
0.0 to 100.0
1.0
Note 1
33
"
db
" (db)
Dead band
Shifts the set value for the cooling proportional band
-50% to 50%
0%
Note 1
34
"
bAL
" (bAL)
Output convergence
value
Offset value for calculating the MV output
value
-100% to 100%
0/50
(single/
dual)
Note 1
35
"
Ar
" (Ar)
Anti-reset windup
Sets the range of integration
0% to 100% FS
100%FS
36
"
rEV
" (rEv)
Sets normal/reverse
operations
Sets the control output to normal or reverse
rv-- (heat (reverse)
/ cool (none))
no-- (heat (normal)
/ cool (none))
rvno (heat (reverse)
/ cool (normal))
norv (heat (normal)
/ cool (reverse))
rvrv (heat (reverse)
/ cool (reverse))
nono (heat (normal)
/ cool (normal))
rv--/rvno
(single/
dual)
37
"
SvL
" (SvL)
SVlimit (lower)
Sets the lower limit for SV
0% to 100% FS
0% FS
Note 2
38
"
Svh
" (Svh)
SVlimit (upper)
Sets the upper limit for SV
0% to 100% FS
100% FS
Note 2
"
TC1
" (TC1)
OUT1 proportion cycle
Sets the proportion cycle of the control output (OUT1)
(Contact, SSR drive)
1 sec to 150 sec
30:Contact
2:SSR drive
Note 3
39
"
TC2
" (TC2)
OUT2 proportion cycle
Sets the proportion cycle of the control output
(OUT2)
(Contact, SSR drive)
1 sec to 150 sec
30:Contact
2:SSR drive
Note 1
"
PLC1
" (PLC1)
OUT1 lower limit
Sets the lower limit of the control output
(OUT1).
-3.0% to 103.0%
-3.0%
40
"
PhC1
" (PhC1)
OUT1 upper limit
Sets the upper limit of the control output
(OUT1)
-3.0% to 103.0%
103.0%
"
PLC2
" (PLC2)
OUT2 lower limit
Sets the lower limit of the control output
(OUT2)
-3.0% to 103.0%
-3.0%
Note 1
"
PhC2
" (PhC2)
OUT2 upper limit
Sets the upper limit of the control output
(OUT2)
-3.0% to 103.0%
103.0%
Note 1
"
PCUT
" (PCUT)
Selects the output limiter type Sets the type of output limiter
0 to 15
0
41
RST
RST
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...