![FujiFilm PXG4 Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483077.webp)
– 76 –
8
Chapter
PV Input Shift
This function shifts PV input before display.
This is used when combining PV input with other instruments.
• Range: -10% to 10% FS
Setting PV Input Shift
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display PvoF ("
PPP
PvvvvooooFFFF
").
3
Press the
key, then use the
keys to
select -5.0 when the bottom part of the display
begins to blink.
PV input shift is set to -5.0°C.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation
mode PV/SV display.
PV shift of -5
°
C
before
shift
after shift
0
PV display
100
°
C
95
°
C
input
SV Offset
This function specifies the SV shift.
This is used to eliminate remaining offset when using P
control.
• Controls act on the calculated SV with SV offset.
• Alarm determination acts on the displayed SV without SV
offset.
• Range: -50% to 50%
Setting SV Shift
The following steps explain how to set SV shift by using 7°C
as an example.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display SvoF ("
SSS
SvvvvooooFFFF
").
3
Press the
key, then use the
keys to
select 7.0 when the bottom part of the display
begins to blink.
SV offset is set to 7.0°C.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
Caution
The SV value in the PV/SV display shows the set value before
the SV offset is added.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...