8-8
8.4 Terminal
Specifications
8.4.1 Terminal
functions
For details about the main and control circuit terminals, refer to Chapter 2, Section 2.3.5 and
Section 2.3.7 (Table 2.8), respectively.
8.4.2 Connection diagram in operation by external signal inputs
(Note 1) Install a recommended molded case circuit breaker (MCCB) or a residual-current-operated
protective device (RCD)/a ground fault circuit interrupter (GFCI)(with overcurrent protection) in
the input (primary) circuit of the inverter to protect wiring. At this time, ensure that the circuit
breaker capacity is equivalent to or lower than the recommended capacity.
(Note 2) A magnetic contactor (MC) should, if necessary, be mounted independent of the MCCB or GFCI
to cut off the power fed to the inverter. Refer to page 9-2 for details. MCs or solenoids that will be
installed close to the inverter require surge absorbers to be connected in parallel to their coils.
(Note 3) For an inverter connected to the power supply of 500 kVA or more (50 kVA or more for single-
phase 115 V class series), be sure to connect an optional DC reactor (DCR).
When connecting a DCR to the inverter, remove the jumper bar from terminals [P1] and [P+].
Note that the terminal assignment of single-phase 115 V class series of inverters differs that of
the above diagram. For details about the terminal assignment, refer to Chapter 10 (page 10-1).
(Note 4)
THR
function can be used by assigning code "9" (Enable external alarm trip) to any of terminals
[X1] to [X3], [FWD] or [REV] (function code E01 to E03, E98, or E99). For details, refer to Chapter
5.
Содержание Frenic Mini FRN001C1E-2U
Страница 60: ...3 15 Figure 3 5 shows the status transition for Menu 1 Data setting Figure 3 5 Data Setting Status Transition ...
Страница 85: ...5 4 ...
Страница 88: ...5 7 ...
Страница 89: ...5 8 C codes Control Functions of Frequency ...
Страница 92: ...5 11 J codes Application Functions y codes Link Functions ...
Страница 167: ...8 6 8 3 Common Specifications ...
Страница 168: ...8 7 ...
Страница 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Страница 172: ...8 11 ...
Страница 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Страница 174: ...8 13 ...
Страница 192: ...MEMO ...
Страница 193: ...MEMO ...
Страница 194: ...MEMO ...
Страница 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...