xii
Geared motors
If the power transmission mechanism uses an oil-lubricated
gearbox or speed changer/reducer, then continuous motor
operation at low speed may cause poor lubrication. Avoid
such operation.
Synchronous mo-
tors
It is necessary to take special measures suitable for this
motor type. Contact your Fuji Electric representative for de-
tails.
In running
special
motors
Single-phase
motors
Single-phase motors are not suitable for inverter-driven
variable speed operation. Use three-phase motors.
* Even if a single-phase power supply is available, use a
three-phase motor as the inverter provides three-phase
output.
Environ-
mental con-
ditions
Installation loca-
tion
Use the inverter within the ambient temperature range from
-10 to +50
q
C(14 to 122
°F
).
The heat sink and braking resistor of the inverter may be-
come hot under certain operating conditions, so install the
inverter on nonflammable material such as metal.
Ensure that the installation location meets the environmental
conditions specified in Chapter 2, Section 2.1 "Operating
Environment."
Installing an
MCCB or
RCD/GFCI
Install a recommended molded case circuit breaker (MCCB)
or residual-current-operated protective device (RCD)/a
ground fault circuit interrupter(GFCI)(with overcurrent pro-
tection) in the input (primary) circuit of the inverter to protect
the wiring. Ensure that the circuit breaker capacity is
equivalent to or lower than the recommended capacity.
Installing an MC
in the secondary
circuit
If a magnetic contactor (MC) is mounted in the inverter's
secondary circuit for switching the motor to commercial
power or for any other purpose, ensure that both the inverter
and the motor are completely stopped before you turn the MC
on or off.
Do not connect a magnet contactor united with a surge killer
to the inverter's secondary circuit.
Installing an MC
in the primary
circuit
Do not turn the magnetic contactor (MC) in the input (primary)
circuit on or off more than once an hour as an inverter failure
may result.
If frequent starts or stops are required during motor opera-
tion, use
FWD
/
REV
signals or the
/
keys.
Combina-
tion with
peripheral
devices
Protecting the
motor
The electronic thermal function of the inverter can protect the
motor. The operation level and the motor type (gen-
eral-purpose motor, inverter motor) should be set. For
high-speed motors or water-cooled motors, set a small value
for the thermal time constant and protect the motor.
If you connect the motor thermal relay to the motor with a
long wire, a high-frequency current may flow into the wiring
stray capacitance. This may cause the relay to trip at a cur-
rent lower than the set value for the thermal relay. If this
happens, lower the carrier frequency or use the output circuit
filter (OFL).
Содержание Frenic Mini FRN001C1E-2U
Страница 60: ...3 15 Figure 3 5 shows the status transition for Menu 1 Data setting Figure 3 5 Data Setting Status Transition ...
Страница 85: ...5 4 ...
Страница 88: ...5 7 ...
Страница 89: ...5 8 C codes Control Functions of Frequency ...
Страница 92: ...5 11 J codes Application Functions y codes Link Functions ...
Страница 167: ...8 6 8 3 Common Specifications ...
Страница 168: ...8 7 ...
Страница 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Страница 172: ...8 11 ...
Страница 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Страница 174: ...8 13 ...
Страница 192: ...MEMO ...
Страница 193: ...MEMO ...
Страница 194: ...MEMO ...
Страница 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...