5-34
E01 to E03,
E98, E99
Terminal [X1] to [X3] Function
Terminal [FWD] and [REV] Function
Function codes E01 to E03, E98 and E99 allow you to assign commands to ter-
minals [X1] to [X3], [FWD], and [REV] which are general-purpose, programmable,
digital input terminals.
These function codes may also switch the logic system between normal and
negative to define how the inverter logic interprets either ON or OFF status of each
terminal. The default setting is normal logic system "Active ON."
To assign negative logic input to any input terminal, set the function code to the
value of 1000s shown in ( ) in Section 5.1 " Function Code Tables." To keep ex-
planations as simple as possible, the examples shown below are all written for the
normal logic system.
Select multi-frequency (1 to 7 steps)--
SS1
,
SS2
, and
SS4
(Function code data = 0, 1, and 2)
㩷
The combination of the ON/OFF states of digital input signals
SS1
,
SS2
, and
SS4
selects one of 8 different frequency commands defined beforehand by 7 function
codes C05 to C11 (Multi-frequency 0 to 7). With this, the inverter can drive the motor
at 16 different preset frequencies.
The table below lists the frequencies that can be obtained by the combination of
switching
SS1
,
SS2
, and
SS4
. In the "Selected frequency" column, "Other than
multi-frequency" represents the reference frequencies defined by frequency
command 1 (F01), frequency command 2 (C30), or others.
Terminal [X3]
(E03)
Terminal [X2]
(E02)
Terminal [X1]
(E01)
2 (
SS4
) 1
(
SS2
) 0
(
SS1
)
Selected frequency
OFF OFF OFF
Other
than
multi-frequency
OFF OFF ON
C05 (Multi-frequency 1)
OFF
ON
OFF
C06 (Multi-frequency 2)
OFF
ON
ON
C07 (Multi-frequency 3)
ON
OFF
OFF
C08 (Multi-frequency 4)
ON
OFF
ON
C09 (Multi-frequency 5)
ON
ON
OFF
C10 (Multi-frequency 6)
ON
ON
ON
C11 (Multi-frequency 7)
Select ACC/DEC time (2 steps)--
RT1
(Function code data = 4)
㩷
Digital input signal
RT1
assigned to the specified terminal on/off may switch com-
binations between acceleration/deceleration time 1 (defined by function codes F07
and F08) and acceleration/deceleration time 2 (defined by E10 and E11).
Turning
RT1
on, for example, enables the inverter to drive the motor using accel-
eration/deceleration time 2.
Содержание Frenic Mini FRN001C1E-2U
Страница 60: ...3 15 Figure 3 5 shows the status transition for Menu 1 Data setting Figure 3 5 Data Setting Status Transition ...
Страница 85: ...5 4 ...
Страница 88: ...5 7 ...
Страница 89: ...5 8 C codes Control Functions of Frequency ...
Страница 92: ...5 11 J codes Application Functions y codes Link Functions ...
Страница 167: ...8 6 8 3 Common Specifications ...
Страница 168: ...8 7 ...
Страница 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Страница 172: ...8 11 ...
Страница 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Страница 174: ...8 13 ...
Страница 192: ...MEMO ...
Страница 193: ...MEMO ...
Страница 194: ...MEMO ...
Страница 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...