The output mode is used to select the proportional
mode (proportional to input differential pressure)
or square root extraction mode (proportinal to
ÀRZ UDWH IRU RXWSXW VLJQDO WR P$ RI WKH
differential pressure transmitter only.
8-1 Change the output mode
In case of square root extraction mode, the cut
point and the mode below the cut point can be
set.
• Under display
d
, press <
INC
! RU
DEC
! IRU
selection of the square root extraction mode
("SQR") or linear mode ("LIN").
8-3 Low cut point setting
The square root extraction mode is selected,
the display
i
is presented and the low cut point
should be set..
Note that if the cut point is set to a small value
around 0%, even a minute differential pressure
FKDQJHFDXVHVDVXGGHQRXWSXWÀXFWXDWLRQ7KH
cut point is used for improving the measurement
LQFDVHRIORZÀRZUDWH
There are two modes :
• On display
, press "CHANGE" to set the low
cut mode
• Under display
, linear or zero output is selec-
table for output below the cut point.
Menu 8 : Output Mode
8: OUTPUT
MODE
XMTR:DP
OUT=LIN
< INC > < CHANGE >
8-1: MODE CHANGE
XMTR : DP
OUT=LIN
< INC > < ENT > < CL >
8-1: MODE CHANGE
XMTR : GP
OUT=LIN
< ENT > < CL >
8-1: MODE
CHANGE
XMTR:DP
OUT=SQR
CHNG OK? < ENT/CL >
8
: OUTPUT MODE
XMTR:GP
OUT=LIN
< INC > < CHANGE >
8-2: MODE
WRITE
XMTR:DP
OUT=SQR
8-3: LOW
CUT
POINT=
XX
.
XX
%FLOW
MODE=
< CHANGE > < CL >
< ENT > < CL >
8-5: POINT
WRITE
XX
.
XX
%FLOW
8-7: LOW CUT MODE
< 1 > LINEAR
< 2 > ZERO
< 1 > < 2 > <CL >
8-7: MODE
CHANGE
LINEAR
CHNG OK? < ENT/CL >
8-8: MODE
WRITE
LINEAR
8-1: MODE CHANGE
XMTR:DP
OUT=LIN
CHNG OK? < ENT/CL >
*1
<OUTPUT MODE
CHANGE>
8-4: POINT
CHANGE
XX
.
XX
%FLOW
8-4: POINT
CHANGE
XX
.
XX
%FLOW
8-6: LOW CUT MODE
ZERO
< CHANGE > < CL >
8-7: MODE
CHANGE
ZERO
CHNG OK? < ENT/CL >
8-8: MODE
WRITE
ZERO
OUT=LIN
8-2: MODE
WRITE
XMTR:DP
OUT=LIN
INC
1
1
INC
(a)
(DP)
GP, AP, LL (Liquid Level)
2
CL
ENT
ENT
5
CL
ENT
3
CL
CL
4
ENT
6
CHNG
CL
CHNG
CHNG
7
ENT
CL
ENT
CL
CL
8
1
OUT=SQR
2
9
CHNG
10
8-6: LOW CUT MODE
LINEAR
< CHANGE > < CL >
11
CL
12
CL
16
ENT
13
CL
2
1
ENT
CL
14
15
17
< INC >
*1
*2 0.00% Cut Point 20.00% FLOW
Note) GP, AP, LL : OUT = LIN only
< DEC > Available Mode
In case of OUT= SQR
In case of OUT=LIN
CHNG
Menu 9
(a)
*2
CHNG OK? < ENT/CL >
= LINEAR or ZERO
Output
Low cut
point
Low cut
point
Output
Differential
input
Differential
input
Fig. A: With linear output
selected in low cut mode
Fig. B: With zero output
selected in low cut mode