![Fuji Electric FCX-AII-V5 series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/fuji-electric/fcx-aii-v5-series/fcx-aii-v5-series_instructions-manual-and-service-instructions_2341970050.webp)
48
TN5FCXA2V5h-E
ZERO
ZERO
ZERO
M
①
②
③
④
⑤
M
M
M
#ANCELTHESETTING
3AVETHESETTING
Menu 6 : Measuring range (LRV, URV)
LRV: Lower range value (0% point)
URV: Upper range value (100% point)
Selectable setting range
/UTPUTM!
526
-AXIMUMMEASURINGRANGE
)NPUT
.ORMAL
ACTION
2EVERSE
ACTION
,26
,26
526
Note) If the set value of the LRV is outside the range,
a setting error also occurs in the URV setting, and
vice versa.
The maximum setting range is ±99999.
The URV may exceed the upper limit depend-
ing on the change of the UNIT. If that happens,
FKDQJHWKH859¿UVW
6-1 : Change of LRV
(lower limit of the measuring
UDQJH P$SRLQW
• Press the key on the screen
c
to display the
screen for setting the zero point range (0% point)
(
d
).
• Input the numerical values with the and keys on
the screen
d
.
Functions of the keys:
key:
To decrease the value.
key: To increase the value.
5DQJH±/59
Note)
If “setERROR” is displayed as a LRV value, the
range value is not supported.
• To set the decimal point position, press the key on
the screen
e
. “P” is displayed at the left of the unit
name (
f
) and you can set the decimal point position
with the and keys.
key: To move the decimal point position to left
key: To move the decimal point position to right
• Select whether the LRV setting is saved on the
screen
g
.
Press the key to save the zero point range setting.
Press the or key to cancel the setting.