In case of level transmitter (FKE)
To avoid any damage of the measuring cell, do not exceed the test pressure
of different cells (please refer to the technical datasheets of the concern trans-
mitter)
Caution
!
Remember !
(6) After assembly, carry out a pressure test. Apply a pressure equal to 150% of the maximum
ZRUNLQJSUHVVXUHWRERWKÀDQJHVLGHKLJKSUHVV3DQGORZSUHVVXUH/PHD
-
surement chamber of the transmitter simultaneously during 15 minutes, and make sure
there is no leakage.
(1) Remove four hexagon
socket head bolts with a
torque wrench, etc..
(2) The process covers, the
O-ring and the bolts and
nuts can now be removed
(3) After disassembly, replace
the faulty part with a new
one.
(4) Before reassembly, clean
carefully the O-ring face of
casing cover with the soft
cloth immersed in water,
alcohol, Freon TF or similar.
(5) Reassemble the detecting unit by reversing the disassembling procedure.
The torque of the bols of the process covers are indicated in the following table.
Bolt size
Bolt material
Tightening torque
Maximum working pressure
0
&U0RVWHHO
1P
8SWRUDWHGÀDQJHSUHVVXUH
0
66
1P
8SWRUDWHGÀDQJHSUHVVXUH
0
66
1P
8SWRUDWHGÀDQJHSUHVVXUH
Seal tape
Bolt
Measurement
chamber cover
Gasket
Seal diaphragm