PARAMETER SETTING PRIOR TO DELEVERY
N°
Item
contents of parameter
1 Damping
value
0,06sec
(time constant)
2
External adjustment function
Adjustable (ENABLE)
of the transmitter
3
Current output mode
Linear (Could be set in factory
when ordering (note 2))
Digital indicator scale
Could be set in factory
(9th digit of code symbol)
when ordering
4
Cut point
7.07%
(square root extraction mode setting)
5
Mode below cut point
Linear
(square root setting)
6
Burnout
Hold (note 3)
7
Polygonal line correction
Not corrected (INVALID)
6DWXUDWLRQFXUUHQW
1RUPDOVSHFL¿FDWLRQ1250$/
9
Protective function of set value
Canceled (OFF)
(write protect)
1RW+&RUWKHORFDOFRQ¿JXUDWRUXQLWZLWK/&'GLVSOD\WRFKDQJHWKHVHWWLQJRIDOOWKHLWHPVH[FHSW
“7: Polygonal line correction,” which can be changed only by the HHC.
Note 2) In both the differential pressure transmitter (Type: FKC) and remote seal type (Type: FKD), the output
current mode is set in linear unless it is designated.
1RWH³+ROG´LVVHOHFWHGIRU³%XUQRXW´XQOHVVRWKHUZLVHVSHFL¿HGE\WKHRUGHU
The damping value (time constant), function of zero/span adjust screw, output current mode,
indicator scale, cut point, mode below cut point and burnout, have been set prior to delivery as
shown in the following.
Each parameter is changed by using HHC or the 3 push button of the LCD display.