![Fuji Electric FCX-AII-V5 series Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/fuji-electric/fcx-aii-v5-series/fcx-aii-v5-series_instructions-manual-and-service-instructions_2341970055.webp)
TN5FCXA2V5h-E
53
M
M
①
②
②
②
M
③
M
④
⑤
⑦
See the next page for the procedure when UNdER is
selected.
M
M
M
⑥
(Cancel the setting)
(Save the setting)
(Cancel the setting)
(Save the setting)
Menu 9 : Burnout direction
Used for selecting output at occurrence of a fault in
the detecting unit.
9-1 bURNoT : Change of burnout
1RW8VHĺ2XWSXWKROG
29(5ĺ29(56&$/(
81'(5ĺ81'(56&$/(
• For NAMUR specification, press the key on the
screen
c
to display the screen for changing the
burnout (
d
).
• Select NotUse, OVER or UNDER on the screen (2)
with the or key and press the key.
• Select whether the burnout setting is saved on the
screen
e
.
Press the key to save the burnout setting.
Press the or key to cancel the setting.
9-2 OVER : Change of burnout current when OVER
(OVERSCALE)
This display appears if you select “OVER” for the
burnout.
• Press the key on the screen
f
to display the
screen for changing the burnout current for OVER-
SCALE (
g
).
• You can change the burnout current with the and
keys on the screen
g
.
Settable range:
For NAMUR specification, 21.6, 21.8, 22.0, 22.2,
22.4, 22.5 can be selected
Note)
You can change the saturation current value
XSSHU OLPLW VHWWLQJ DW ³- 9DOXH DQG VSHFL¿FD
-
tion of saturation current.”
• Select whether the burnout current setting is saved
on the screen
i
.
Press the key to save the burnout current setting
for OVERSCALE.
Press the or key to cancel the setting.