66
TN5FCXA2V5h-E
(
Save the setting
)
(
Cancel the setting
)
M
M
⑨
⑩
⑩
⑪
M
J-3 SPEC : Selection of the burnout & saturation cur-
UHQWYDOXHVSHFL¿FDWLRQ
QRUPDOVSHFL¿FDWLRQH[SDQG
-
HGVSHFL¿FDWLRQ
• Press the
key on the screen
k
to display the
screen for selecting the burnout & saturation current
YDOXHVSHFL¿FDWLRQ
l
).
6HOHFW³1R50$/QRUPDOVSHFL¿FDWLRQ´RU³(;3H[
-
panded specification)” on the screen
l
with the
and keys.
Select “NoRMAL” for the normal setting.
Select “EXP” for the expanded setting.
* To change the saturation current value (upper limit,
ORZHUOLPLWVHOHFWWKHH[SDQGHGVSHFL¿FDWLRQ
Normal
VSHFL¿FDWLRQ
([SDQGHGVSHFL¿FDWLRQ
Saturation
current value
(lower limit)
3.8 mA
¿[HG
3.2 mA to 4.0 mA
Settable in increments of
0.1 mA
Saturation
current value
(upper limit)
20.8 mA
¿[HG
20.0 mA to 21.6 mA
Settable in increments of
0.1 mA
The table below lists the output current value for
burnout (OVER, UNDER).
1RUPDOVSHFL¿
-
cation
([SDQGHGVSHFL¿FDWLRQ
Burnout
(UNDER)
3.2 to 3.8 mA
3.2 mA to saturation current
value (lower limit)
Burnout
(OVER)
20.8 to 21.6 mA
Saturation current value
(upper limit) to 21.6 mA
The values in the table above can be set in increments
of 0.1 mA.
• Select whether the NoRMAL/EXP setting is saved on
the screen .
Press the key to save the NoRMAL/EXP setting.
Press the or key to cancel the setting and return
to the screen
k
.
Содержание FCX-AII-V5 series