WIRING
4
(1) Application of a voltage exceeding 60 V DC or 40 V AC (exceeding 33 V DC or 23 V AC
when arrester equipped) between “
+
” and “
–
” terminals may result damage to the transmit-
ter.
(2) Use a shielded cable for the transmission line where possible.
(3) Avoid installing signal and power cable in thev same conduit or cable tray in order to avoid
electromagnetic interferences..
In case of explosion proof, wiring shall be made in accordance with the
UHOHYDQWUHJXODWLRQVWRHQVXUHWKHH[SORVLRQSURR¿QJ
Improper wir
LQJFDQFDXVHDULVNRIH[SORVLRQ¿UHDQGRWKHUVHULRXVDFFL
-
dents.
Cautions on wiring
DANGER
• Before making wiring work, be sure to turn OFF the main power to prevent
electrical shocks.
• Use wiring materials of correct rating to prevent accidents.
8VHFRUUHFWSRZHUVRXUFHWKDWPHHWVWKHVSHFL¿FDWLRQVWRSUHYHQW¿UHV
• Field ground according the recommendations of electrical connections.
$IWHULQVWDOOLQJWKHWUDQVPLWWHUIFKHFNWDKWDOOFRYHUVDUH¿UPO\FORVHGWR
protect the transmitter agains water ingress.
CAUTION