Effective July 1, 1992, the United States clean air act
governs the disposal of refrigerants such as R-134a.
Therefore, when discharging or purging the sealed
system use an EPA approved refrigerant recovery
system as outlined in the final rule on the protection of
stratospheric ozone and refrigerant recycling, which
was published in the Federal Register May 14, 1993.
Section 4 Refrigeration
4-1
IMPORTANT
Instructions given here are furnished as a guide.
Persons attempting to use these instructions to make
repairs to the sealed refrigeration system should have
a working knowledge of refrigeration and previous
training on sealed system repair, and an EPA
certification for servicing refrigeration systems.
NOTE
Electrolux Home Products Inc. does not permit the use
of recovered refrigerant in the servicing of our
products for in-warranty and out-of-warranty repairs or
for products covered by service contracts. Therefore,
only new refrigerant or refrigerant that has been
reclaimed back to new specifications by a refrigerant
manufacturer is to be used.
NOTE
Definitions
Recovery:
To remove refrigerant in any condition from a system
and store it in an external container without necessarily
testing or processing it in any way.
Recycling:
To clean refrigerant for reuse by oil separation and
single or multiple passes through devices, such as
replaceable core filter-driers, which reduce moisture,
acidity and particulate matter. This term usually applies
to procedures implemented at the field job site or at a
local service shop.
Reclaim:
To reprocess refrigerant to new product specifications by
means which may include distillation, will require
chemical analysis of the refrigerant to determine that
appropriate product specifications are met. This term
usually implies the use of processes or procedures
available only at a reprocessing or manufacturing facility.
Safety Warnings
Compressor Testing
Whenever testing a compressor, extreme caution
should be used to prevent damaging the terminals. A
compressor with a damaged terminal or a grounded
winding can expel a terminal from its insulated housing
when the compressor is energized. If this happens, a
mixture of refrigerant and oil will be released that could
be ignited by an external heat source (open flame,
heater, etc.). Also, if there is air in the system when this
happens, a spark at the compressor shell could ignite the
refrigerant and oil mixture.
Charging Sealed Systems
Overcharging a refrigeration system with refrigerant can
be dangerous. If the overcharge is sufficient to immerse
the major parts of the motor and compressor in liquid
refrigerant, a situation has been created which, when
followed by a sequence of circumstances can lead to the
compressor shell seam separating.
A hydraulic block occurs, preventing the compressor
from starting. This condition is known as locked rotor.
Electric current continues to flow through the
compressor motor windings which become, in effect,
electric resistance heaters. The heat produced begins to
vaporize the excess refrigerant liquid causing a rapid
increase in system pressure. If the compressor
protective devices fail, the pressure within the system
may rise to extremes far in excess of the design limits.
Under these conditions, the weld seam around the
compressor shell can separate with explosive force,
spewing oil and refrigerant vapor which could ignite.
To eliminate this exceedingly rare but potential hazard,
never add refrigerant to a sealed system. If refrigerant is
required, evacuate the existing charge and recharge with
the correct measured amount of the refrigerant specified
for the system.
Содержание FFH17F8HW0
Страница 2: ......
Страница 14: ...Section 2 Installation Information 2 6 Notes ...
Страница 18: ...Section 3 Electronic Control 3 4 Notes ...
Страница 33: ...Section 4 Refrigeration 4 15 HFC 134a CFC 12 Pressure Temperature Chart ...
Страница 36: ...Section 4 Refrigeration 4 18 Notes ...
Страница 48: ...Section 5 Component Teardown 5 12 Notes ...
Страница 53: ...Section 7 Wiring Diagram 7 1 ...
Страница 54: ...Section 7 Wiring Diagram 7 2 Notes ...