Table 2: Maximum Motor Cable Length (in feet*)
Controller Model
Franklin Electric
Motor Model
HP
AWG 600V Copper Wire Sizes, 167
o
F (75
o
C) Insulation
14
12
10
8
6
4
SubDrive15 C
234 514 xxxx
1.5 (1.1 kW)
420
670
1060
-
-
-
SubDrive20 C
234 315 xxxx
2.0 (1.5 kW)
320
510
810
1000
-
-
SubDrive30 C
234 316 xxxx
3.0 (2.2 kW)
240
390
620
990
-
-
SubDrive50 C
234 317 xxxx
5.0 (3.7 kW)
-
230
370
590
920
-
MonoDrive C
214 505 xxxx
214 507 xxxx
214 508 xxxx
0.5 (0.37 kW)
0.75 (0.55 kW)
1.0 (0.75 kW)
400
300
250
650
480
400
1020
760
630
-
1000
990
-
-
-
-
-
-
MonoDriveXT C
214 508 xxxx
224 300 xxxx
224 301 xxxx
1.0 (0.75 kW)
1.5 (1.1 kW)
2.0 (1.5 kW)
250
190
190
400
310
250
630
480
390
990
770
620
-
1000
970
-
-
-
*1 ft = 0.305 m
NOTES:
• The use of 600 V minimum rated motor cable is required.
• SubDrive models show cable lengths for highest power motor supported by each model.
• A 10-foot (3.05 m) section of cable is provided with the SubDrive/MonoDrive to connect the analog pressure transducer.
• Maximum allowable wire lengths are measured between the controller and motor.
• Aluminum wires should not be used with the SubDrive/MonoDrive.
• All wiring to comply with the National Electrical Code and local codes.
• MonoDrive minimum breaker amps may be lower than AIM Manual specifications for the motors listed due to the soft-
starting characteristic of the MonoDrive controller.
• SubDrive minimum breaker amps may appear to exceed AIM Manual specifications for the motors listed because
SubDrive controllers are supplied from a single-phase service rather than three-phase.
• Motor Overload Protection Note: The drive electronics provide motor overload protection by preventing motor current
from exceeding the maximum Service Factor Amps (SFA). Motor overtemperature sensing is not provided by the drive.
• Flat-jacketed submersible motor cable is recommended. All splices in the motor cable must be properly sealed with the
appropriate watertight shrink tubing. Extreme caution must be taken, especially when using non-jacketed motor cable,
to avoid damaging or compromising the motor cable insulation during installation
or service. Improper splicing or damage to motor cable insulation may expose the conductor(s) to moisture and can
produce motor cable failure.
Generator Sizing
Basic generator sizing for the Franklin Electric SubDrive/MonoDrive system is 1.5 times
the maximum input watts consumed by the drive, rounded up to the next normal-sized
generator.
Recommended minimum generator sizes:
MonoDrive C
1/2 hp = 2000 Watts (2 kW)
3/4 hp = 3000 Watts (3 kW)
1 hp = 3500 Watts (3.5 kW)
MonoDriveXT C
1.5 hp = 4000 Watts (4 kW)
2 hp = 5000 Watts (5 kW)
SubDrive15 C
= 3500 Watts (3.5 kW)
SubDrive20 C
= 5700 Watts (6 kW)
SubDrive30 C
= 7000 Watts (7 kW)
SubDrive50 C
= 11000 Watts (11 kW)
NOTE:
Not to be used on a Ground Fault Circuit Interrupter (GFCI). If using an externally regulated generator, verify that the
voltage, Hertz and idle speed are appropriate to supply the drive.
Содержание 5870205003C
Страница 1: ...Owner s Manual SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R ...
Страница 45: ...NOTES ...
Страница 46: ...SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R Manual del propietario ...
Страница 90: ...NOTAS ...
Страница 91: ...Manuel du propriétaire SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R ...
Страница 135: ...REMARQUES ...