Operating Manual BKS601C
23
8.2
Configuring the Electronic Unit
Prior to the initial calibration, the following settings must be applied (ref. to
„9. Parametrization“ and „15. Technical Reference“):
System parameters
Language
Desired display language
Service parameters
Motor config.
1)
Standard
Length of rail left
(only if left rail is used)
Length of rail right
(only if right rail is used)
Sensor covered
depending on sensor used
Sensor uncovered
depending on sensor used
Sensor range
depending on sensor used
1)
only if no steering frame is used
Parameters BKS601C
Control mode
Detection requirements (Edge left or right, Centre or Line
guiding)
Dead band
Set at default value 0.1mm
Analog output
2)
Control output
2)
or
Feedback Sensor
Manual output
2)
Signal value at manual operation (dependent from
equipment)
Offset output
2)
Set at default value 0
Output limit
2)
Set at default value 100.0%
P value output
2)
Set at default value 1.00
I value output
2)
Set at default value 1.00
Config. output
2)
Range of output signal for actuator (dependent from
equipment)
Control output
2)
Polarity of output signal (set to standard)
2)
only if analog control output is used
Caution
Wrong parameter settings may cause malfunction of the electronic unit or the total
system. The parameter setting must be performed with reasonable care before start-
up.