Operating Manual BKS601C
36
I value output
Use:
If the parameter
analog output
is set to
control output
, this parameter
defines the I-fraction of the PI-controller.
This parameter can be changed during automatic operation.
Range:
0.01
to
320.00
Default:
1.00
Increment:
0.01
Unit:
[s]
Configuration output
Use:
This parameter defines the range of the actuator signal for the analog
output (control output).
If the parameter
analog output
is set to
Feedback Sensor
, it defines
the range of the signal.
Range:
0...10V and 0...20mA,
Default:
0...10V
0...10V and 4...20mA, ±10V
and
0…20mA
Control meaning output
Use:
With this parameter, the polarity of the actuator signal can be
changed and so also control system can be inverted.
Range:
Standard,
Inverted
Default:
Standard