Alarm list supply air and extract air fans
Error
code
Fault
number
Alarms
Cause of problem
14
4
Phase missing
Network phase loss or too high supply voltage imbalance.
Check the supply voltage. See parameter 14-12.
11
7
DC overvoltage
The intermediate circuit voltage is higher than the threshold value.
10
8
DC undervoltage
The intermediate circuit voltage drops below the threshold value for low voltage
warning.
9
9
Converter overloaded
The load exceeds 100 % over too long a period.
8
10
Overheating
The motor has overheated because load has exceeded 100 % for too long.
See parameter 1-90.
7
11
Thermistor alarm
The thermistor or thermistor connection is disconnected.
See parameter 1-90.
5
13
Overvoltage
The inverter's upper current limit has been exceeded.
2
14
Earth fault
Discharge from output phases to ground.
12
16
Short circuit
Short circuit in motor or on motor terminal blocks.
4
17
Communication error
No communication with frequency converter. See parameter group 8-0X.
19
30
Phase U is missing
Motor phase U is missing Check the phase. See parameter 4-58.
20
31
Phase V is missing
Motor phase V is missing Check the phase. See parameter 4-58.
21
32
Phase W is missing
Motor phase W is missing Check the phase. See parameter 4-58.
17
38
Internal error
Contact FläktGroup support.
28
44
Earth fault
Discharge from output phases to ground.
23
47
Fault 24VDC
24 V DC supply may be overloaded.
25
48
Low control voltage
Low control voltage. Contact FläktGroup support.
15
51
AMA fault
The settings for motor voltage, motor current and motor output are
probably incorrect. Check the settings.
25
59
Current limit
The current is higher than the value in parameter 4-18, Current limit.
44
60
External stop
External stop has been activated. To resume normal operation, power the terminal
block that is programmed for External stop with 24 V DC and reset the frequency
converter (via serial communication, digital I/O or by pressing the reset button on
the keypad).
1
69
Temperature alarm
The temperature sensor on the power card is either too hot or too cold.
29
80
Reset alarm
Restores all parameters to their factory-set values.
47
87
DC Brake
The frequency converter has DC braking.
40
95
Incorrect load
The torque is lower than the torque level set for no
load, which indicates a broken belt. See parameter group 22-6.
PM-Motors with FC101, FC102 and FC106
14