Air handling unit
Cooling recovery
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
HREC CLG RECOVERY
Start Outdoor temperature > Room temperature
+ 2K and
Room temperature > Room se 1K
Stop Outdoor temperature
≤
Room temperature
or
Room temperature
≤
Room setpoint
Filter alarm
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 1
Ú
FILTER ALARM
The filter alarm on the eQ PRIME is always
activated at the factory (Supply air-AI+Extract
air-AI)
CO
2
control
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
FAN COMP AIR QUAL
IPSUM
MAIN INDEX
Ú
CONFIGURATION
Ú
INTEGRATIONS
Ú
IPSUM SYSTEM
Function:
The fan and/or temperature setpoints are
controlled to achieve minimum energy
consumption by the IPSUM system
Humidity control mode
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
HUM CONTROL MODE
For control mode function see page 34
[ref to Humidity control].
Humidity control UNIT
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
HUM CONTROL UNIT
Change between absolute or relative humidity
setpoint.
Dehumidity or temperature
priority
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
DEHUM TEMP PRIO
Give the temperature setpoint priority over
the humidity setpoint.
If heating valve position reaches 90 % it
will reduce the dehumidification.
Deviation alarm
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
HUM DEVIATION ALARM
Activation of humidity deviation alarm.
9