27
FläktGroup
DC_9355GB 20180119_R0
We reserve the right to make changes without prior notice
Air handling unit
Boost
Boost
is a function that ensures comfortable room
temperature when the unit is started normally via internal
schedulers. This function is not activated from
the factory, but can easily be activated on site. See page
38.
MAIN INDEX
Ú
CONFIGURATION
Ú
CONFIGURATION 2
Ú
BOOST
Optimised start of heating and cooling is activated
separately.
Optimised start of cooling is activated when:
• Room temperature > Start stpt c Hysteresis.
• The time until start via internal schedulers
< Compensation time.
Optimised start of cooling is deactivated when:
• Room temperature < Start stpt cooling.
Optimised start of heating is activated when:
• Room temperature < Start stpt h Hysteresis.
• The time until start via internal schedulers
< Compensation time.
Optimised start of heating is deactivated when:
• Room temperature > Start stpt heating.
If the function is activated without the room temperature
sensor connected, the measured value from the air
temperature sensor will be used instead. This function is
always included in eQ PRIME.
Boost
Start stpt cooling
Start stpt heating
Hysteresis
Compensation time
15.0 °C
25.0 °C
0.5 °C
60 min
9