Unit shutdown
The external stop signal (e.g. for fire damper exer-cising)
is factory set to NO. The contact function can easily be
changed from the menu.
MAIN INDEX
Ú
UNIT
Ú
INPUTS
Ú
DIGITAL INPUTS
Ú
EMERGENCY STOP
Bypass
The bypass damper shall be controlled by external fire
controller. The air handling unit fans can be configured to
handle higher temperatures for shorter times by acti-
vating Fire mode. For the EC-motor no activation is needed.
To activate this fire mode in the inverter(Danfoss) go to
MAIN INDEX
Ú
UNIT
Ú
FAN CONTROL
Ú
FIREMODE, DANFOSS
When function Fire mode is activated the fan operation are
not reduced by high temperature or stopped by internal
alarms.
Note: If the inverter is damaged in this mode the warranty
ceases to apply.
Settings for operation and fan speed can be set in the Fan
control menu:
MAIN INDEX
Ú
UNIT
Ú
FAN CONTROL
Fan speed when activating the digital fire input 1 for fire/
smoke in the extract air:
Supply fan fire setpoint 1
default value 80 %
Exhaust fan fire setpoint 1
default value 80 %
Fan speed when activating the digital fire input 2 for fire/
smoke in the supply air:
Supply fan fire setpoint 2
default value 0 %
Exhaust fan fire setpoint 2
default value 0 %
Air handling unit
Fan control
Fan control
Supply fan
Exhaust fan
Actual step
Firemode, Danfoss
Fire mode 1
Supl.Fan fire setp.1
Exh.Fan fire setp.1
Supl.Fan fire setp.2
Exh.Fan fire setp.2
Fire mode 2
Rundown time el htg
Disable high speed
Op hours settings
Fan override
Flow control, unit
off
off
off
yes
Run Both
80 %
80 %
0 %
0 %
Run Both
180 sec
-40.0 °C
Auto
1/s
9