38
FläktGroup
DC_9355GB 20180119_R0
We reserve the right to make changes without prior notice
Air handling unit
Settings can be done in the Heat recovery damper menu:
MAIN INDEX
Ú
UNIT
Ú
TEMP CONTROL
Ú
HREC DAMPER
There is a lower limit for the outdoor air flow during mixing
in the controller. This limit can be set in sevral ways.
Parameter
Unit
Description
Min fresh air
%
Limitation of the the mixing
controller output value.
Min flow fresh air
l/s
A controller is controlling
the minimum amount of
outdoor air in l/s to the
supply air.
Air quality setpoint
ppm
The air quality setpoint in
the room is limiting the
active mixing controller
output. See page 34 for
air quality settings.
Active mixing pressure balancing
The settings for pressure balancing can be found in the
Balance control menu:
MAIN INDEX
Ú
UNIT
Ú
DAMPER CONTROL
Ú
BALANCE CONTROL
Prs.balance setpoint
is the setpoint when pressure
balancing over mixing damper. When the pressure is
within the setpoint as near as the max deviation, Max Bal.
Prs. deviation, the mixing damper is starting to open. If
the setpoint is not achieved within a time period, Max Bal.
control time, the mixing damper is opened.
Balance control
Prs.balance setpoint
Force damp. at start
Max Bal.control time
Max Bal. Prs. deviation
Balance Control Exh.
Min. Prs.balance Exh.damp
Exh.Bal. Contrl. Invert
Pres.balance Exh.damp
Balance Control outsideAir
Pres.balance Outsidedamp
Min. Prs.balance Outs.damp
Outs.Bal. Contrl. Invert
10 Pa
60 sec
60 sec
10Pa
100 %
50 %
Active
0 %
100 %
0 %
50 %
Active
9