Fire protection unit
If a
fire protection unit
is to be connected, it may be
necessary to adjust the parameters. The control unit in eQ
PRIME supports connection of the following signals:
• Fire alarm
• Unit shutdown (damper exercise)
• Alarm from fire protection unit
Different signals can be connected depending on the type
of
fire protection unit
used. The table below shows available
signals and their connection to eQ PRIME.
Fire protection unit with eQ Prime bypass
eQ PRIME with bypass and seprate fire modes, can
distinguish fire alarm in supply air and extract air.
For this, seperate fire protection units in supply air and
extract air is needed.
See table below for connection to eQ:
Fire alarm
The
fire alarm
is factory-configured to NC, but a bracket on
the terminal block prevents the alarm from going off when
there is no extinguishing equipment. The contact function
or alarm delay can easily be changed from the menu.
MAIN INDEX
Ú
UNIT
Ú
INPUTS
Ú
DIGITAL ALARMS
Ú
FIRE
Air handling unit
Fire alarm mode
For each fire input, it is possible to select a fire mode.
Alarm from fire protection unit
To receive a B alarm from the
fire protection unit,
e.g.
for an internal error, a digital or universal input must
be reconfigured on the control unit. If both the external
schedulers are not used, the function of one of them
can be changed, e.g. digital input 3 (D3). The process is
described below.
1. Log in as administrator (password 8888)
2. Go to MAIN INDEX
Ú
UNIT
Ú
CONFIGURATION
Ú
CONFIGURATION 1
3. Change EXT. CONTROL INPUT to ONE
4. Go to MAIN INDEX
Ú
UNIT
Ú
CONFIGURATION
Ú
CONFIGURATION 2
5. Change AUXILIARY INPUTtoALARM
6. Change RESTART to EXECUTE
7. Log in as administrator (password 8888)
8. Go to MAIN INDEX
Ú
UNIT
Ú
CONFIGURATION
Ú
CONFIGURATION IO's
Ú
DIGITAL ALARMS
9. Change AUX. ALARM to DI3
10. Go back to MAIN INDEX
Ú
UNIT
Ú
CONFIGURATION
Ú
CONFIGURATION IO's
11. Change RESTART to EXECUTE
12. Log in as usual (password 2000)
13. Go to MAIN INDEX
Ú
UNIT
Ú
AUXILIARY
Ú
ALARM INPUT and set the desired
CONTACT FUNCTION
Note that external control input 1 will now control against
the fan step indicated by the parameter Fan Step, see page
22.
Do not hesitate to contact FläktGroup support for advice or help
with configuration. Tel. +46 36 193003.
Parameter
Description
InActv
The fire mode is inactive
Stop
The unit will stop
Run Sply
The supply fan will run in fix speed and the exhaust fan
will stop
Run Exh
The exhaust fan will run in fix speed and the supply fan
will stop
Run Both
Both fan will run in fixed speed
Ctrl St1
The fans will keep to run to fan setpoint Step 1
Ctrl St2
The fans will keep to run to fan setpoint Step 2
Fire protection
unit
Fire
alarm
Alarm
from fire
protection
unit
Unit
shutdown
ABAV-S3
73-74
69-70
N/A
FCMA-2
73-74
69-70
71-72
FICO-128
73-74
69-70
71-72
Fire protection
unit
Fire
alarm
Alarm
from fire
protection
unit
Unit
shutdown
ABAV-S3 for supply air
detector
127-128
69-70
N/A
ABAV-S3 for extract/
room air detector
73-74
69-70
N/A
FCMA-2 for supply air
detector
127-128
69-70
71-72
FCMA-2 for extract/
room air detector
73-74
69-70
71-72
FICO-128 for supply air
detector
127-128
69-70
71-72
FICO-128 for extract/
room air detector
73-74
69-70
71-72
9