Air handling unit
Loop controllers
From the
Loop controllers
menu, you can adjust all
thecontrollers for the control unit.
MAIN INDEX
Ú
UNIT
Ú
LOOP CONTROLLERS
This menu contains settings for Gain, integration time
constant and derivative time constant. Note that the
gain must be negative for cooling but positive for other
controllers.
However, the cascade controller settings are different
from the other settings. In this case, it is not possible to
set the actual PID controller. Instead, High limit and Low
limit can be set for the supply air temperature. It is also
possible to set Load compensation, which causes constant
offsetting of the cascade controller's output signal (i.e. of
the calculated supply air setpoints).
Loop controllers
0%
Supply fan
Exhaust fan
Casc controller tmp
Heat recovery
Heating
Heating frost
Cooling
0%
0%
0%
0%
0%
20.0 °C
22.0 °C
Auxiliary
The control unit has various auxiliary functions. These
functions are managed from the
Auxiliary
menu.
MAIN INDEX
Ú
UNIT
Ú
AUXILIARY
The eQ PRIME is delivered with only the configurable
operating mode output activated. For this reason, setting
and reading of this function should be done via the
Auxiliary
menu.
This output can be very useful if the unit's operation will
affect other equipment.
Do not hesitate to contact FläktGroup support for advice and
assistance. Tel. +46 36 193003.
Auxiliary
Op mode output
Op mode outp select
On
Off