28
FläktGroup
DC_9355GB 20180119_R0
We reserve the right to make changes without prior notice
Air handling unit
Main setpoints
To set the desired
Main
setpoints
for temperature and
fans, go to:
MAIN INDEX
Ú
UNIT
Ú
SETPOINTS/SETTINGS
This menu shows the
Main setpoints
for temperature
and fans. Go to All settings to access the settings
for sub-level functions. The content of this menu is
changed according to the selected temperature and
fan control settings. The active operating mode from
the internal schedulers is shown directly under All
settings.
Temperature setpoints
• Heating setpoint for comfort operation
(Comfort htg stpt)
• Heating setpoint for economy operation
(Economy htg stpt)
• Dead zone between heating and cooling during
comfort operation (Comfort tmp deadz)
• Dead zone between heating and cooling during
economy operation (Economy tmp deadz)
• Lowest permitted supply air temperature
(Supply tmp min stpt)
• Highest permitted supply air temperature
(Supply tmp max stpt)
Note: Cooling setpoint = Heating se dead zone.
Fan setpoints
• Setpoint supply air fan step 1 (Sply fan st1 stpt)
• Setpoint supply air fan step 2 (Sply fan st2 stpt)
• Setpoint extract air fan step 1 (Exh fan st1 stpt)
• Setpoint extract air fan step 2 (Exh fan st2 stpt)
Note: Fan setpoints are given in either l/s or
Pa, depending on the activated control function.
Important!
Remember that electric heaters require at least one
minimum air flow value.
Refer to the minimum flows in the table on the next
page.
Main setpoints
All settings
Time switch program
Comfort htg stpt
Comfort tmp deadz
Comfort htg stpt
Economy tmp deadz
Supply tmp min stpt
Sply fan st1 stpt
Sply fan st2 stpt
Supply tmp max stpt
Comf St1
22.0 °C
22.0 °C
22.0 °C
22.0 °C
22.0 °C
250l/s
600l/s
22.0 °C
250l/s
600l/s
Exh fan st1 stpt
Exh fan st2 stpt