45
FläktGroup
DC_9355GB 20180119_R0
We reserve the right to make changes without prior notice
ReCooler HP
ReCooler HP
The ReCooler HP is an integrated reversible cooler.
Depending if the air handling unit is in heating or cooling
demand the ReCooler HP will alter between cooling and
heating mode.
Defrost fan compensating
Under some conditions the ReCooler HP will go to a defrost
mode during a couple of minute. During this time the
fans will go on reduced speed. This reduced fan speed
is configurable for each fan. The settings are 20-100 % of
actual fan setpoint.
MAIN INDEX
Ú
UNIT
Ú
TEMP CONTROL
Ú
COOLING
The ReCooler HP status is shown in the eQ display, such
as the cooling/heating demand and the actual operating
status. If there is an alarm in the ReCooler HP, it could be
viewed in the eQ display.
Cooling
Controller
Output signal
40%
Disable by outs tmp
12.0 °C
Act. Opstatus
Alarm number
LowEnv.limit
0%
Stop
Alarm
Description
No alarm
No alarm
Rotor alarm
Rotor alarm
Comp. alarm
Compressor start alarm
Diff.press alarm
Differential pressure alarm
Max.pressure
Max. Discharge pressure alarm
Inverter alarm
Frequency drive (power+) alarm
Inverter offline
Frequency drive offline alarm
Min.pressure
Min. Suction pressure alarm
EEV fault
Expansion valve alarm
(sensor)
Discharge temp
Discharge temperature alarm
(sensor)
Discharge press
Discharge pressure alarm
(sensor)
Suction pressure
Suction pressure alarm
(sensor)
Superheat alarm
Low superheat alarm
High env. limit
High envelope limit
(pressure)
Low env. limit
Low envelope limit
(pressure)
10