Proprietary and Confidential
Wiring
34
Overlapping outputs
Certain outputs can be grouped to overlap timings. For example, an interrupted (non-continuous) pilot is
connected to terminal 17 alone (PILOT OUTPUT). For an intermittent (continuous) pilot, jumper terminals 17
(PILOT OUTPUT) and 18 (UPSTREAM MAIN OUTPUT) to combine the timings of the two outputs. This means
the pilot will remain energized from the start of PTFI until the sequence ends.