Sequence of operation
18
Purge
LED STATE
When feedback is received to confirm that the actuator is at
the purge position, input must be received from the air
switch on terminal 14 (SAFETY LIMIT INPUT) within the
actuator travel time duration (timing t11). If the fan LED is
blinking, the control is waiting for this input. If the fan LED is
solid, this input has been received and the control is
counting the purge time (timing t1).