Wiring
29
Disable air switch check
Place a wire jumper from terminal 11 to terminal 13 to
disable the air switch check. This is the check to verify that
the air switch is changing states between cycles. This
satisfies the check by using the line voltage that is provided
by terminal 11 while in standby (to send the actuator to the
economy position) to indicate that the air switch normally
closed switch position has power.