Sequence of operation
17
Safety limits input
The safety limits must all be proven within the amount of
time specified for actuator travel time (timing t11). The count
begins when feedback is received to indicate that the
actuator is at the high fire position for purging.
The BurnerPRO will lockout if this input is not proven within
the specified duration.