Valve proving
Pressurization test time
Following the pressurization, a test is performed for a set amount of time to ensure that the gas
pressure switch changes to the normally open state. This time period may be adjustable and is
normally around 25 seconds. If the test fails, the flame safeguard will lockout. This lockout indicates
that the downstream valve may be leaking since the space in between is losing pressure.
41
NORMALLY OPEN
PRESSURE >= SETPOINT
CLOSED
CLOSED