Sequence of operation
24
Main trial for ignition (MTFI)
LED STATE
After timing t7 ends, the state will change from MTFI to
PTFI. MTFI will last for the duration of timing t5.
Terminal 16 (IGNITION OUTPUT) is not energized during
PTFI. Terminal 17 (PILOT OUTPUT) will remain energized
for the duration of timing t9. Terminals 18 and 19
(UPSTREAM and DOWNSTREAM MAIN OUTPUT) will
remain energized from the start of MTFI until the sequence
ends.
The transition from PTFI to MTFI is indicated by the shift
from a blinking flame LED (PTFI) to a solid flame LED
(MTFI).