Sequence of operation
27
Postpurge
LED STATE
Upon a loss of the call for heat, the control will postpurge for
the duration of timing t6. During postpurge, terminals 18 and
19 (UPSTREAM and DOWNSTREAM MIAN OUTPUT) are
de-energized. Terminals 6 and 7 (FAN OUTPUT) remain
energized until the end of postpurge. Terminal 11
(ACTUATOR ECONOMY OUTPUT) is energized to drive
the actuator to the economy position.