Sequence of operation
20
Driving actuators to ignition
LED STATE
After the purge timing is complete, the BurnerPRO will drive
the actuator to the ignition position. The output for terminal 9
(ACTUATOR HIGH FIRE OUTPUT) is no longer powered.
Instead, terminal 10 (ACTUATOR LOW FIRE OUTPUT) is
powered instead as the BurnerPRO is commanding the
actuator to the ignition position.
The LEDs for actuator open and actuator closed will
alternate as the control waits for feedback on terminal 8
(ACTUATOR FEEDBACK INPUT).
ALTERNATE