Proprietary and Confidential
Sequence of operation
22
Pilot trial for ignition (PTFI)
LED STATE
After timing t3’ ends, the state will change to PTFI. PTFI will
last for the duration of timings TSA’ plus t7, and a flame
signal must be detected during PTFI. The flame signal can
be from either the UV flame detector input or from the flame
rod input.
Terminal 16 (IGNITION OUTPUT) will remain energized
until the end of timing TSA’. Terminal 17 (PILOT OUTPUT)
will remain energized past the end of PTFI, for the duration
of timing t9 into the MTFI state.
BLINK
Содержание BurnerPRO
Страница 1: ...BURNERPRO TROUBLESHOOTING August 2020...
Страница 2: ...Proprietary and Confidential Sequence diagram 2 Without valve proving Interrupted pilot...
Страница 3: ...Proprietary and Confidential Sequence diagram 3 With valve proving...
Страница 5: ...Proprietary and Confidential Terminal designations 5 Without valve proving...
Страница 6: ...Proprietary and Confidential Terminal designations 6 With valve proving...
Страница 43: ...Proprietary and Confidential Valve proving BurnerPRO The Smart LEDs indicate the lockout code 43...
Страница 45: ...Proprietary and Confidential Valve proving BurnerPRO The Smart LEDs indicate the lockout code 45...
Страница 47: ...THANK YOU...