46
Festo — MSE6-E2M — 2022-08d
Commissioning
6. Set the IP addressing with DIL switch 3.
7. Fit the cover.
8. Screw on the retaining screws hand-tight and then tighten to 0.4 Nm ± 10%.
Setting operating mode and protocol, DIL switch 1
The energy efficiency module only supports the Remote I/O operating mode with the bus node
CPX-FB36, factory setting.
All 1.1 and 1.2 switch elements of DIL switch 1 must be in the OFF position.
DIL switch 1.1
Setting operating mode
DIL 1.1: OFF
Factory setting
‘Remote I/O’ operating mode.
All functions of the energy efficiency module are controlled directly
by the controller or by a higher-level PLC.
DIL 1.1: ON
Not supported.
The 1.1 DIL switch element must be in the OFF position.
Tab. 30: Setting the operating mode with DIL switch 1.1
DIL switch 1.2
Setting the protocol
DIL 1.2: OFF
Factory setting
‘EtherNet/IP’ protocol.
The energy efficiency module uses the ‘EtherNet/IP’ protocol.
DIL 1.2: ON
Protocol ‘Modbus TCP’
The energy efficiency module uses the ‘Modbus TCP’ protocol.
Tab. 31: Setting the protocol with DIL switch 1.2
Setting diagnostic mode, DIL switch 2
DIL switch 2
Setting diagnostic mode
DIL 2.1: OFF
DIL 2.2: OFF
Factory setting
‘I/O diagnostics interface’ and status bits are switched off, + 0 byte
I/0 byte O.
DIL 2.1: OFF
DIL 2.2: ON
The status bits are on, + 1 byte I/0 byte O
1)
.