Festo — MSE6-E2M — 2022-08d
Commissioning
39
1
2
3
4
Fig. 22: DIL switches on bus node CPX-M-FB13
1
DIL switch 1: operating mode
2
DIL switch 2: Reserved
3
DIL switch 3, element 8: diagnostic mode
4
DIL switch 3, element 1... 7: station number
Setting the operating mode with DIL switch 1
The energy efficiency module only supports the Remote I/O operating mode with the bus node
CPX-FB13, factory setting.
All switch elements of the DIL switch 1 must be in the OFF position.
DIL switch 1
Description
DIL 1.1: OFF
DIL 1.2: OFF
Factory setting
Remote I/O operating mode
All the functions of the energy efficiency module are controlled
directly by the PROFIBUS master.
DIL 1.1: ON
DIL 1.2: OFF
Not supported by the energy efficiency module.
DIL switch elements 1.1 and 1.2 must be in the OFF position.
DIL 1.1: OFF
DIL 1.2: ON
DIL 1.1: ON
DIL 1.2: ON
Tab. 22: Setting the operating mode with DIL switch 1
DIL switch 2
All switch elements of DIL switch 2 must be in the OFF position, factory setting.
Setting station number and diagnostic mode, DIL switch 3
Station numbers may only be assigned once per controller.