66
Festo — MSE6-E2M — 2022-08d
Parameterisation
Module parameter: upper pressure limit value
Function number
4828 + m * 64 + 13 (low byte)
4828 + m * 64 + 14 (high byte)
m = module number 1
Description
An upper pressure limit can be set for the module.
Values
2-byte value: low byte + 256 * high byte
Default: 32767, low byte = 255; high byte = 127
Permissible values: 0 … 32767
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29
If the pressure P2 according to the parameterised unit exceeds the parameter-
ised upper critical limit, the diagnostic message FN10 is output if the monitor
limit values parameter is active.
The monitoring of limit value violation only becomes active after the expiry of
the time set in the monitor critical limit values parameter startup.
Tab. 53: Upper pressure limit value module parameter
Module parameter: upper limit value pressure change
Function number
4828 + m * 64 + 15 (low byte)
4828 + m * 64 + 16 (high byte)
m = module number 1
Description
An upper limit value for the pressure change can be set for the module.
Values
2-byte value: low byte + 256* high byte
Default: 32767, low byte = 160 = 0xA0; high byte = 15 = 0x0F
Permissible values: 0 … 32767
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN25
If the amount of the pressure change set according to the parameterised unit
exceeds the parameterised critical limit, the diagnostic message FN10 is output
if the monitor limit values parameter is active.
The monitoring of limit value violation only becomes active after the expiry of
the time parameterised in the diagnostics limit value parameter startup. The
monitoring function is only active if the shut-off valve is in the blocking state,
Em.3.0 = 1.
Tab. 54: Upper limit value pressure change module parameter
Содержание MSE6-E2M
Страница 1: ...MSE6 E2M Energy efficiency module Operating instruc tion 8163321 2022 08d 8163323...
Страница 83: ......