5. Diagnostics and error handling
5−12
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 2 Position record error
CPX error group 102
(CPX−MMI: [Record error])
No.
Message
Cause/description
Error handling
Type
1)
21
Invalid record number
At the start there was
an invalid record
number (0 or > 64).
·
Check the record
number and correct
(first transfer record
number, then starting
edge).
Error
level: F1
Reset: R
22
Record is not configured
Called record was not
configured and does not
contain valid positioning
data.
·
Check record and
parameterise.
Error
level: F1
Reset: R
23
Position set is locked
The called record is not
enabled for execution.
·
Check the positioning
record and enable.
Error
level: F1
Reset: R
24
Record switching is not
possible
The demanded switch
ing condition is invalid.
·
Check the switching
condition and correct.
Error
level: F1
Reset R
Switching parameter
ised in record 64.
·
Remove switching
condition in record 64
and correct record
list, if necessary.
Reset: R
The selected switching
condition is not
permissible when using
a DSMI. The DSMI does
not support force
control.
·
Correct the switching
condition.
The selected switching
conditions are only al
lowed in a positioning
record with force con
trol.
·
Check the positioning
record and correct.
1)
For the error level and reset type, see section 5.2.3.
Содержание CPX-CMAX-C1-1
Страница 2: ......
Страница 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Страница 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Страница 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Страница 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Страница 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Страница 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Страница 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...