5. Diagnostics and error handling
5−20
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 4 System error A
CPX error group 104
(CPX−MMI: [System error A])
Continued
No.
Message
Cause/description
Error handling
Type
1)
44
Teaching not possible
2)
Teaching (falling edge at
CPOS.TEACH) was trig
gered accidentally due to
breaking a connection or
switching off the control.
·
Only activate
CPOS.TEACH = 1 (pre
pare teaching) directly
before the teaching
operation. Always end
teaching immediately.
Error
level: F1
Reset: R
Teaching is not possible
in direct mode.
·
Change operating
mode.
Teaching during active
commissioning function
not possible.
·
End commissioning
function first.
In commissioning oper
ating mode, the teaching
target in parameter 1 is
invalid.
·
Correct parameter 1.
Without a reference,
teaching is not possible.
·
Before teaching,
carry out homing.
Lower software end
position is greater
than/equal to the
upper software end
position for teaching
the software end posi
tion in commissioning
operating mode. It is
not accepted.
·
First teach the upper
software end posi
tion.
·
Correct the teaching
position.
Continued ...
Upper software end
position is less than/
equal to the lower soft
ware end position for
teaching the software
end position in commis
sioning operating mode.
It is not accepted.
·
First teach the lower
software end posi
tion.
·
Correct the teaching
position.
1)
For the error level and reset type, see section 5.2.3.
2)
For an exact cause, see the diagnostic memory.
Содержание CPX-CMAX-C1-1
Страница 2: ......
Страница 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Страница 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Страница 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Страница 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Страница 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Страница 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Страница 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Страница 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...