3.3.2 Periphery fault (PF)
If an error is recognized by the bus node of the CP
system, a periphery fault will be triggered, depending
on the setting of DIL switch element 2. The error will
then be transferred to the interface module and dis-
played.
Possible
causes
DIL switch
element 2
Selection
No.
Error
Errors
1 and 2
are not
transmitted
1
Voltages for valves below
tolerance (< 21.6 V)
2
Voltage for valves switched off
(e.g. EMERGENCY STOP)
Factory
setting:
All errors
1 ... 5
are
transmitted
3
Supply to inputs/sensors
switched off
(e.g. internal fuse triggered)
4
Short circuit or overload at
digital outputs
5
CP connection interrupted
The system is not stopped by a periphery fault. A reac-
tion can be programmed (e.g acknowledge errors, stop
running system, restart system).