Connecting the continuing remote field bus
Continuing
remote field bus
Pin no. *
Designation
Meaning
1
DO
Data out
2
/DO
Data out inverse
3
DI
Data in
4
/DI
Data in inverse
5
Earth/GND
Reference conductor
9
RBST
Bridge to pin 5
Sleeve
Screening
Screening/shielding
* Do not connect pins not listed here
Pin selection
Part no.
9-pin plug with pin insert,
screened/shielded with sleeve/housing.
Possible designs:
a) straight socket
b) angled socket
c) angled socket
(locking)
a) RC-09 P 1 N 128 049
b) RC-09 P 1 N 12T 049
c) RC-09 P 3 N 12T 0Z0
Cable selection
LIYCY 3x2x0.25 mm
2
IBS RBC METER-T
28 06 28 6
9
8
7
6
5
4
3
2
1
1. Installation
CP FB6-E 9809c
1-13