3.1.4 Diagnostic bus LEDs
The table below shows the possible INTERBUS specific
LED displays on the operating status of the CP node:
1. Error displays RC, BA, RD;
( = lights up;
= LED flashes; = out)
LEDs
Operating status
Error treatment
RC
BA
RD
String x
Valve test mode is switched on.
If valves do not switch:
- CP connection is interrupted
- hardware error
•
Check CP connecting cable
•
Servicing required
RC
BA
RD
String x
Valve test mode is switched on
or
string assignment of CP system
has been modified
Exit the self test by switching off
the operating voltage
or
check/correct string assignment,
or
press the SAVE button in order
to save the new string
assignment
RC
BA
RD
INTERBUS fault,
either:
- bus not connected or
interrupted
- interface switched off
•
Check or connect
bus cable
•
Programmed switch off
by master
•
Reset status on IBS
RC
BA
RD
No data transfer
Check operating status
of module
Table continued on next page
3. Diagnosis
3-6
CP FB6-E 9809c
Содержание Compact Performance CP-FB6-E
Страница 1: ...Compact Performance CP fieldbus node 6 Programming and diagnosis Fieldbus protocol INTERBUS...
Страница 11: ...Contents and general safety instructions X CP FB6 E 9809c...
Страница 12: ...Chapter 1 Installation 1 Installation CP FB6 E 9809c 1 1...
Страница 29: ...1 Installation 1 18 CP FB6 E 9809c...
Страница 30: ...Chapter 2 Commissioning 2 Commissioning CP FB6 E 9809c 2 1...
Страница 58: ...Chapter 3 Diagnosis 3 Diagnosis CP FB6 E 9809c 3 1...
Страница 70: ...Appendix A Technical appendix A Technical appendix CP FB6 E 9808c A 1...