Diagnostic messages
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
91
Diagnostic messages of the CMMP-AS-...-M3
No.
Reaction
Actions
Causes
Message
Code
08-9
7389
h
Angle encoder at
[X2B] is not sup-
ported
Angle encoder type read
at [X2B], which is not sup-
ported or cannot be used
in the desired operating
mode.
–
Incorrect or inappro-
priate protocol type
selected?
–
Firmware does not
support the connec-
ted encoder model?
Depending on the
additional information of
the error message
footnote
6)
:
•
Load appropriate firm-
ware.
•
Check/correct the
configuration for en-
coder evaluation.
•
Connect an appropri-
ate encoder type.
Config-
urable
6)
Additional information (PNU 203/213):
0001: HIPERFACE: encoder type is not supported by the firmware -> connect another encoder type or load more recent firmware,
if applicable.
0002: EnDat: The address space in which the encoder parameters would have to lie does not exist with the connected EnDat
encoder -> check the encoder type.
0003: EnDat: encoder type is not supported by the firmware -> connect another encoder type or load more recent firmware, if
applicable.
0004: EnDat: Encoder rating plate cannot be read from the connected encoder. -> Change encoder or load more recent firmware,
if applicable.
0005: EnDat: EnDat 2.2 interface parametrised, connected encoder supported but only EnDat2.1. -> Replace encoder type or
reparameterise to EnDat 2.1.
0006: EnDat: EnDat2.1 interface with analogue track evaluation parametrised, but according to rating plate the connected
encoder does not support track signals. -> Replace encoder or switch off Z0 track signal evaluation.
0007: Code length measuring system with EnDat2.1 connected, but parametrised as a purely serial encoder. Purely serial evalu-
ation is not possible due to the long response times of this encoder system. Encoder must be operated with analogue track
signal evaluation -> connect to analogue Z0 track signal evaluation.