Functions
64
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
Digital I/O
Function
Standard DIN
DIN0 … DIN3
Position selector, selection of the positioning records (0 … 15)
configurable
DIN 4
Fix: Output stage enable (POWER ENABLE)
DIN 5
Fix: Controller enable (CONTROLLER ENABLE)
DIN 6
Fix: Limit switch negative (LIMIT 0)
DIN 7
Fix: Limit switch positive (LIMIT 1)
DIN 8
Configurable
DIN 9
Configurable high-speed input
(Sample input/reference switch)
Standard DOUT
DOUT0
Fix: Controller operational (READY)
DOUT1
Configurable
DOUT2
Configurable (optional: DIN10)
DOUT3
Configurable (optional: DIN11)
Additional DIN
DIN10 (DOUT2)
Configurable
DIN11 (DOUT3)
Configurable
DIN12 (AIN1)
Configurable – trigger level at 8 V
DIN13 (AIN2)
Configurable – trigger level at 8 V
Tab. 6.26 Assignment DIN/DOUT
Activated signal inputs require calculation time of the motor controller.
Therefore, do not deactivate required signal inputs.
Functions of the digital inputs
Note
Multiple assignments of digital inputs are tolerated by the firmware.
Execution of the function with multiple assignment depends on the respectively set
operating mode.
•
Check carefully whether your combination of input signals makes sense.
Function assignment is dependent on:
–
the control interface used
–
the selected operating mode
–
the number of freely usable inputs.
To control additional functions via digital inputs, you can change the factory-set
assignment of the digital inputs present at the basic unit.