![Festo CMMO-ST-C5-1-LKP Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/festo/cmmo-st-c5-1-lkp/cmmo-st-c5-1-lkp_original-instructions-manual_2283105016.webp)
3 I-Port
16
Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
3
I-Port
The Festo-specific I-Port interface is used for exchange of serial data from decentralised function mod
ules (devices) at field level.
The LED C/Q on the motor controller displays the status of the I-Port connection.
3.1
IO-Link/I-Port and digital I/O interface [X1]
Port
Pin
Function
X1
1
11
1
11
1
+24 V (OUT)
24 V
tial-free relay contact for the controller
enable input
2
0 V (GND)
Reference potential for output signals
3
DOUT2
Output 2, parameterisable
4
DOUT1
Output 1, parameterisable
5
READY
Output Ready
6
ENABLE
Controller enable input
7
–
No function, not connected internally
8
–
9
L–
0 volt (GND)
10
C/Q
IO-Link/I-Port signal
11
L+
24 volt supply of the I-Port IC, not con
nected to the logic supply at X9
1)
Not overload-proof, max. 100 mA
2)
Required signals for controller enable can be parameterised (FCT)
è
3)
Pins can be used for the 4th and 5th conductor of the I-Port / IO-Link cable
Tab. 3.1
Port X1 I/O interface, pin 9 ... 11 allocated for IO-Link