B Reference
paramete
126
Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
PNU 503
Max. permitted acceleration (Max. Acceleration)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw2
Reading or parameterisation of the max. permitted acceleration [SINC/s²].
Tab. B.80
PNU 503
B.4.11
Project data – force/torque mode
PNU 510
Stroke limiter (Stroke Limitation)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw1
Reading or parameterisation of the max. permitted displacement (stroke) [SINC] with active force
control.
With active force control, the actual position relative to the start position must not change by more
than the amount specified in this parameter. In this way, you can ensure that the axis will not perform
an uncontrolled movement if force control is activated by mistake (e.g. workpiece missing).
Monitoring can be deactivated with CDIR.XLIM = 1.
Tab. B.81
PNU 510
PNU 512
Max. permitted force (Max. Force)
Subindex 1
Class: Var
Data type: int32
FW …
Access: rw1
Reading or parameterisation of the max. current (force) [mA], with which the motor may be operated.
The value is always positive. Internally, this limits the max. “positive” and “negative” current.
Tab. B.82
PNU 512