6
Diagnostics
138
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
Diagnostic messages and fault clearance
3Fh
Record invalid
Definable as:
F
/-/-
Diagnostic memory: optional
The started record is invalid. The record data is implausible or the record type is invalid.
Check parameters of the record.
– Resettable: Error can be reset immediately.
Definable error response(s): B, C, D,
E
, F, G
40h
Last teaching not successful
Definable as: -/
W
/I
Diagnostic memory: optional
Teaching of the current positioning record is not possible.
The current positioning record must be of the type 'position record'.
– If defined as a warning: The warning is no longer active when the following TEACH attempt is suc
cessful or a switch takes place from the Teach mode (mode 1) to normal operation (mode 0).
41h
System reset
Definable as:
F
/-/-
Diagnostic memory: always
An internal firmware error has been detected.
Contact Festo Service.
– Resettable: Error can be reset immediately.
Definable error reaction(s): A
43h
FCT connection without master control
Definable as: -/
W
/I
Diagnostic memory: optional
There is no longer a connection to the FCT, e.g. the cable was disconnected.
Check the connection and perform a reset, if necessary.
– For parameterisation as a warning: The warning disappears if the connection to the FCT is re-es
tablished.
44h
Parameter file not compatible with firmware
Definable as: -/
W
/I
Diagnostic memory: always
The parameter file that was just written to the device is not suitable for the firmware of that device.
As much data as possible is automatically taken over from the parameter file. Parameters that are
not initialised through the parameter file are imported from the default parameter file. If new firm
ware software is required, all parameters might not be written.
Load a valid parameter file into the device.
– If defined as a warning: The warning disappears when a new parameter file is successfully written.
4Dh
Bootloader memory error
Definable as:
F
/-/-
Diagnostic memory: always
In the boot procedure, a defective memory cell was detected.
Perform a firmware update. If the error is still present, the memory might be faulty. Then the
device must be replaced.
– Resettable: Cannot be reset; software reset is necessary.
Definable error reaction(s): A