- at location G62 open circuit - trim air valve flap position arrow
breaker 37HN moves to C.
- (at location G65 open circuit
breaker 41HN).
On maintenance panel 472VU:
- BULK/CARGO (FWD/CARGO) MFA comes
on.
- close circuit breaker 37HN (41HN). - BULK/CARGO (FWD/CARGO) MFA remains
on.
3. On maintenance panel 472VU:
- press MFA RESET pushbutton - BULK/CARGO (FWD/CARGO) MFA goes
switch 20WB. off.
4. On COMPT TEMP panel 437VU: On COMPT TEMP panel 437VU:
- release BULK CARGO/ISOL VALVE - OFF/R legend comes on.
(FWD CARGO/ISOL VALVE) push- - for duration of isolation valve
button switch 6HN (52HN). flap movement, ISOL VALVE push-
button switch FAULT legend comes
on and then goes off.
On R ECAM display - AIR COND page:
- isolation valve closed,
- isolation valve color : amber.
On maintenance panel 472VU:
A310-200 AMM - CARGO COMPARTMENT
TEMPERATURE CONTROL - ADJUSTMENT/TEST
Revision 32.0
P.Blk EFFECTIVITY: FED ALL
21-64-00-05
Printed - Date: 12/11/12 Time:
Copyright © 12 FedEx Express Corporation, Memphis TN, 38194, All rights reserved.
Page 8 of 106
JUN 01/2012