Table 330.3.1 shows the number of solenoids and automatic timer controller outputs for the standard
Gold Series
models. For GS2 through GS60 models, there are at least as many timer outputs as there
are solenoids. Each timer output connects to an individual solenoid. For GS72 through GS120 models,
there are more solenoids than timer outputs. These models also have two headers (compressed air
reservoirs). If your collector is one of these models, you must connect some of the timer outputs to two
solenoids. When you connect a timer output to two solenoids, make sure the solenoids are connected to
diaphragm valves on different headers, as shown in Figure 330.3.3.
20
Figure 330.3.3 - DOUBLE UP TIMER OUTPUTS
AIR LINE
1/4" OD
TUBE
SOLENOID BOX
ELECTRICAL
TIMER
DIAPHRAGM
SOLENOID
TIMER OUTPUT
HEADER
HEADER
GS2
2
6
10
10
N
GS4
4
6
10
10
N
GS6
6
6
10
10
N
GS8
4
6
10
10
N
GS10
5
6
10
10
N
GS12
6
6
10
10
N
GS16L
8
10
10
10
N
GS16 SQ
4
10
10
10
N
GS20
5
10
10
10
N
GS24
6
10
10
10
N
GS32
8
10
10
10
N
GS36
12
22
20
20
N
GS48
16
22
20
20
N
GS60
20
22
20
20
N
GS72
24
22
20
20
Y
GS84
28
22
20
20
Y
GS96
32
22
20
20
Y
GS108
36
22
20
20
Y
GS120
40
22
20
20
Y
No. of Timer Outputs
Double
Timer
outputs
GOLD SERIES TIMER REQUIREMENTS
Table 330.3.1
Model
Designation
No. of
Solenoids/
Diaphragms
Determinator
Dwyer
T4 & P4