THIS SETTING CONTROLS THE HIGH PRESSURE
ALARM. SETTING SHOULD BE ABOVE 6.
THE IDC WILL CLEAN THE FILTERS BASED ON PRESSURE
READINGS. THE LO P SETTING WILL STOP THE CLEANING SYSTEM
WHEN IT REACHES THIS PRESSURE - FACTORY DEFAULT = 2
THE IDC WILL CLEAN THE FILTERS BASED ON PRESSURE
READINGS. THE HI P SETTING WILL START THE CLEANING SYSTEM
WHEN IT REACHES THIS PRESSURE - FACTORY DEFAULT = 3
CYL DN = Y
ON = .XXX
ACCEPT
HI P = X.X
ACCEPT
LO P = X.X
CHANGE
ACCEPT
NO CYL = X
NUMBER OF CYCLES
SKIP IF CYL DN = N
CYL DN = N
NO
DO YOU WANT EXIT PROGRAM MODE? PRESS VALUE
KEY IF YES -PRESS ITEM UP KEY TO MOVE BACK TO
PREVIOUS OPTIONS
YES
LOW PRESSURE ALARM
SET POINT
RANGE =.5 TO 15 IN WG
ALM.L = --.--
EXIT
ACCEPT
HIGH PRESSURE ALARM
SET POINT
RANGE =.5 TO 15 IN WG
ALM.H = X.X
ACCEPT
OFF = XXX
PULSE FREQUENCY
(OFF TIME)
RANGE 7.0-999 SEC
ACCEPT
TO "C"
ITEM
ITEM
ITEM
ITEM
ITEM
ITEM
ITEM
VALUE
ITEM
ITEM
VALUE
ITEM
VALUE
VALUE
ITEM
VALUE
ITEM
VALUE
ITEM
VALUE
ITEM
VALUE
CHANGE
CHANGE
CHANGE
CHANGE
CHANGE
TO "A"
WHEN CYCLE DOWN IS ENABLED USE THE UP AND DOWN VALUE KEYS TO SET
THE NUMBER OF CLEAN DOWN CYCLES UP TO A MAX OF 15. THE IDC WILL
STEP THROUGH THE CYCLE AND SHUT ITS SELF OFF WHEN FINISHED.
LOW PRESSURE SET POINT
FOR PULSE ON DEMAND
CLEANING FUNCTION
HIGH PRESSURE SET POINT
FOR PULSE ON DEMAND
CLEANING FUNCTION
PULSE DURATION (ON TIME)
RANGE = .01 - .50 SEC
THIS SETTING CONTROLS HOW LONG A PULSE LASTS - ITS
DURATION. SHOULD BE SET AT 0.200 IN MOST APPLICATIONS.
THIS SETTING CONTROLS THE TIME BETWEEN PLUSE EVENTS -
ITS FREQUENCY. SHOULD BE SET AT 15 IN MOST APPLICATIONS.
THIS SETTING CONTROLS THE LOW PRESSURE ALARM.
SETTING SHOULD BE BELOW THE HIGH PRESSURE
ALARM SET POINT AND BELOW THE LO P SETTING.
TO "B"